ZigBee device list
Motion detector | Smoke sensor |
---|---|
Door detector | Water Detector |
Temperature and Humidity Sensor | CO Sensor |
These ZigBee node devices support ZHA standard protocol.
Linker ZigBee gateway module is one kind of Linker modules which can communicate with up to 32 ZigBee node devices. It is powered by Marvell 88MZ100 ZigBee microcontroller SoC chip. This ZigBee offers advantages for many application scenarios, including lighting control, smart metering, home/building automation, remote controls and health care applications.
Tutorial
we will show how to interface Deepcam ZigBee sensors using the Linker ZigBee gateway.
Prerequisites
Commands to communicate with ZigBee sensor
1. Set Permit Join
Attribute Name | Type | Note |
---|---|---|
CMD Length | Uint8 | 0x02 |
CMD ID | Uint8 | 0x75 |
Permit Join | Uint8 | 0x00 – Always off; 0xFF – Always on; Other values – Turn on permit join for a period of time |
Example
- Send: [UART] 02 75 1E
- Success response: [UART] 02 8A 00
Note: How to reset ZigBee node device and let it join into the ZigBee gateway?
- Insert the pin to the reset hole and hold, until the green light is blinking very fast.
- If the light blinking is not fast, just release the pin and insert it again until it is blinking very fast.
- This will set the ZigBee sensor into reset mode.
- Send Set Permit Join commands to join
- After a while, gateway will get the response–** New Device Joined Indication**
2. New Device Joined Indication
Sent after ZigBee gateway sends Transport Key to the joining device or received a ZDP Device Announcement.
Attribute name | Type | Note |
---|---|---|
CMD Length | Uint8 | 0x0E |
CMD ID | Uint8 | 0xFC |
Flag | Uint8 | 0x02 |
Sub CMD ID | Uint8 | 0xE1 -Gateway Special command |
Short Addr | Uint16 | |
IEEE MAC Addr | Uint64 | |
Capability | Uint8 | 0xFF – If this indication is sent after Transport Key; Other values – If this indication is sent after receiving the joining device’s Dev Annce |
Example Transport Key has been sent to a node whose short address is 0x443B and IEEE address is 00:50:43:C9:9F:21:90:6C [UART] 0E FC 02 E1 3B 44 6C 90 21 9F C9 43 50 00 FF
3. Get Gateway MAC Address
Get Gateway IEEE Address Request
Attribute name | Type | Note |
---|---|---|
CMD Length | Uint8 | 0x02 |
CMD ID | Uint8 | 0x14 |
Sub CMD ID | Uint8 | 0x6F |
Get Gateway IEEE Address Response
Attribute name | Type | Note |
---|---|---|
CMD Length | Uint8 | 0x0C |
CMD ID | Uint8 | 0x15 |
Flag | Uint8 | 0x02 |
Reserved | Uint8 | 0x00 |
Sub CMD ID | Uint8 | 0x6F |
IEEE MAC Address Length | Uint8 | 0x08 |
IEEE MAC Addr | Uint64 |
Example
- Send: [UART] 02 14 6F
- The Gateway’s IEEE Address is 00:50:43:C9:9F:26:9E:4D [UART] 0C 15 00 6F 08 4D 9E 26 9F C9 43 50 00
4. Set APS Header Parameters
Note:Before sending any other commands in this section, the first step is to set the APS(Application Support Sublayer) Header parameters for the next ZCL(ZigBee Cluster Library) command.
Attribute name | Type | Note |
---|---|---|
CMD Length | Uint8 | 0x0C |
CMD ID | Uint8 | 0xFC-ZCL Request |
Flag | Uint8 | 0x02-ZCL Special Command |
Sub CMD ID | Uint8 | 0x01 – Set APS Params |
Profile ID | Uint16 | 0x0104 -Home Automation |
Src Endpoint | Uint8 | |
Dest Endpoint | Uint8 | Fixed to 0x02 for group mode |
Dest Addr Mode | Uint8 | 0x01-group address; 0x02 – node short address |
Dest Addr | Uint16 | |
Tx Options | Uint8 | 0x02 |
Radius | Uint8 | 0x0A |
Example
- Set source endpoint to 0x01, destination endpoint to 0x01, destination address to 0xAE3E. [UART] 0C FC 02 01 04 01 01 01 02 3E AE 02 0A
- Success response: 04 FD 02 01 00
5. ZDP bind
ZDP(ZigBee Device Profile) Bind Request
Attribute name | Type | Note |
---|---|---|
CMD Length | Uint8 | 0x16 |
CMD ID | Uint8 | 0xD8 |
Source IEEE Address | Uint64 | |
Source Endpoint | Uint8 | |
Cluster ID | Uint16 | |
Destination Address Mode | Uint8 | 0x01 – 16-bit group address for Destination Address and Destination Endpoint Not present;0x03 – 64-bit extended address for Destination Address and Destination Endpoint present |
Destination Address | Uint64 | |
Destination Endpoint | Uint8 |
Example:
- Send: [UART] 16 D8 69 53 37 53 C9 43 50 00 01 05 00 03 1D 4F 28 0F C9 43 50 00 01
- Response: [UART] 02 D9 00
6. Read ZCL Attribute Request and response
Request
Attribute name | Type | Note |
---|---|---|
CMD Length | Uint8 | 0x08 |
CMD ID | Uint8 | 0xFC |
Flag | Uint8 | 0x00-From ZCL Client to ZCL server |
Cluster ID | Uint8 | 0x00 0x05 |
Command ID | Uint16 | 0x00 |
Attribute Number | Uint8 | 0x01 |
Start Attribute ID | Uint16 | 0x01 0x00 |
Response
Attribute name | Type | Note |
---|---|---|
CMD Length | Uint8 | 0x08 |
CMD ID | Uint8 | 0xFC |
Flag | Uint8 | 0x03 |
Cluster ID | Uint8 | 0x00 0x05 |
Command ID | Uint8 | 0x01 |
Attribute ID | Uint16 | 0x01 0x00 |
State | Uint8 | 0x01 |
Data type | Uint8 | 0x31 |
Zone Type | Uint16 |
Example
- Send: [UART] 08 FC 00 00 05 00 01 01 00
- Success respone: [UART] 0B FE 03 00 05 01 01 00 00 31 28 00
Zone Type
Sensor Name | Zone Type |
---|---|
Door Detector | 0x15 0x00 |
Motion Detector | 0x0d 0x00 |
Water sensor | 0x2a 0x00 |
Smoke sensor | 0x28 0x00 |
7. Report configuration
Request
Attribute name | Type | Note |
---|---|---|
CMD Length | Uint8 | 0x18 |
CMD ID | Uint8 | 0xFC |
Flag | Uint8 | 0x00 |
Cluster ID | Uint8 | 0x01 0x00 |
Command ID | Uint8 | 0x06 |
Attribute Number | Uint8 | 0x01 |
Attribute ID | Uint16 | 0x21 0x00 |
Data Type | Uint8 | 0x20- Uint8 |
Minimal Reporting Time | Uint16 | 0x0A 0x00 |
Maximum Reporting Time | Uint 16 | 0x0A 0x00 |
Data | Uint8 | 0x01 |
Timeout | Uint16 | 0x00 0x00 |
Response
Attribute name | Type | Note |
---|---|---|
CMD Length | Uint8 | 0x06 |
CMD ID | Uint8 | 0xFD |
Flag | Uint8 | 0x00 |
Cluster ID | Uint8 | 0x01 0x00 |
Command ID | Uint8 | 0x06 |
State | Uint8 | 0x00 |
Example
-
Send: [UART] 11 FC 00 01 00 06 01 00 21 00 20 0a 00 0e 00 01 00 00
-
Success response: [UART] 06 FD 00 01 00 06 00
8. Device Alarm Reporting
Attribute name | Type | Note |
---|---|---|
CMD Length | Uint8 | 0x15 |
CMD ID | Uint8 | 0xFE |
Flag | Uint8 | 0x01 |
Cluster ID | Uint8 | 0x00 0x05 |
Command ID | Uint8 | 0x00 |
Source Endpoint | Uint8 | 0x01 |
Source address type | Uint8 | 0x02-Short address |
Source address | Uint16 | |
Reserved | Uint32 | 0x00 0x01 0x00 0x00 |
Zone State | Uint16 | 0x21 0x00 |
Reserved | Uint24 | 0x00 0x00 0x00 |
Example [UART]15 FE 01 00 05 00 01 02 7B D0 00 D0 00 01 00 00 21 00 00 00 00 00
Sensor state
Sensor Name | Open/Activated |
---|---|
Door Detector | 0x20 0x00 |
Motion Detector | 0x21 0x00 |
Water sensor | 0x21 0x00 |
9. Battery level reporting
Attribute name | Type | Note |
---|---|---|
CMD Length | Uint8 | 0x13 |
CMD ID | Uint8 | 0xFE |
Flag | Uint8 | 0x03 |
Cluster ID | Uint8 | 0x01 0x00 |
Command ID | Uint8 | 0x0A |
Source Endpoint | Uint8 | 0x01 |
Source address type | Uint8 | 0x02-Short address |
Source short address | Uint16 | |
Unkown | Uint16 | 0x00 0x4B |
Reserved | Uint32 | 0x00 0x01 0x00 0x00 |
Zone State | Uint16 | 0x21 0x00 |
Data Type | Uint8 | 0x20-Uint8 |
Battery Level | Uint8 |
Example Receive: [UART] 13 FE 03 01 00 0A 01 02 6D 4B 00 4B 00 01 00 00 21 00 20 BC
Battery level = (0xBC/2) %= 94%
10. Unbind Device
Request
Attribute name | Type | Note |
---|---|---|
CMD Length | Uint8 | 0x0C |
CMD ID | Uint8 | 0xE4 |
IEEE Address | Uint64 | 0x00 0x00 0x00 0x00 0x00 0x00 0x00 0x00 |
Type | Uint8 | 0x00 |
Target Short Address | Uint16 | |
Source Endpoint | Uint8 | 0x01 |
Reponse
Attribute name | Type | Note |
---|---|---|
CMD Length | Uint8 | 0x0A |
CMD ID | Uint8 | 0x7B |
IEEE Address | Uint64 | |
Type | Uint8 | 0x00 |
Example
- Send: [UART] 0C E4 00 00 00 00 00 00 00 00 00 AA BB
-
Response: [UART] 0A 7B 69 53 37 53 C9 43 50 00 00
Note: When you use gateway send command to ZigBee node device and want it response, you have to make sure the ZigBee node device is not in sleep mode, or you will always fail to communication with ZigBee node device. You can click the reset hole to activate the ZigBee node device.
For more details,please refer to original post
https://github.com/YaoQ/zigbee/blob/master/zigbee-sensor-tutorial.md